![Two Channel Controller TOPAX DE](uploads/2016/08/products69_crop_400_400_rel_center_middle.jpg)
In a Nutshell
Technical Details
Display and controls |
|
||
---|---|---|---|
Measuring input for free chlorine Measuring cell-options |
Amperometric 2-electrode measuring cells, measuring range adjustable from 0 … 10 mg/l | ||
Amperometric 3-electrode measuring cell with potentiostatic control, measuring range adjustable from 0 … 2 mg/l | |||
Diaphragm-covered measuring cell, 0/4 … 20 mA, measuring range according to the sensor (max. 10 mg/l) |
|||
Further measurement inputs |
|
||
Digital inputs | Inputs for:
|
||
Connection of the inputs and outputs | By means of terminal blocks, max. 1 mm2 | ||
Control characteristic for 2 inputs (disinfection and pH value) |
|
||
Disturbance variable (optional) | 0/4 … 20 mA programmable, disturbance factor: 0.1 … 10 times amplification | ||
Controller outputs (each as per the configuration) |
3 digital outputs, optocoupler, 48 V DC; 250 mA, pulse frequency 10 … 350 pulses/min. | ||
5 relay outputs programmable as
|
|||
Analogue outputs 0/4 … 20 mA, max. load 500 Ohms | |||
Alarm output | Relay output as collective alarm for the measured variables of free chlorine, pH value, Redox potential, temperature as potential free changer | ||
Measurement value alarm, min. and max. alarm freely adjustable. Time delay adjustable max. 200 minutes | |||
Safety cutout To prevent overdosing (Y-alarm), time delay adjustable: max. 200 minutes |
|||
Current outputs for remote transfer of the measured value to the inputs | Current outputs for each measured value 0/4 … 20 mA possible spreading; max. load 500 Ohms potential free | ||
Significant geometric spreading: >50 % with measuring input free chlorine and 0/4 … 20 mA >10 % during measurement input of pH value and Redox potential |
|||
Interface (optional) | Modbus protocol via RS 485 | ||
Load capacity of the relay | 230 V / 50 Hz, 3 A | ||
Protection class | IP65 with locked screw connections | ||
Ambient temperature | °C | -5 … +45 | |
Supply voltage | VAC | 90 … 264, short circuit and overload-proof | |
Power consumption | VA | 24 | |
Housing dimensions | mm | 302 x 231 x 107 (W x H x D) wall-mounted housing | |
Weight | kg | 2 … 2.5 |
Subject to technical changes
Download
BA: Operation instruction
PI: Product information